KW1 series ACB
 
Application
KW1 series ACB are designed for control and protection of L.V. power distribution network. They are installed in L.V. distribution board as main switches.
Technical Data
w Rated AC current: 630A~5000A
w Short-circuit breaking capacity: 80kA~120kA
w Rated operational voltage: AC690V or below
w Number of poles: 3 / 4
w Draw-out type or Fixed type are provided
w Multi-functional intelligent controller
w In compliance with IEC60947-2, GB14048.2
|
Type
|
KW1-2000
|
KW1-3200
|
KW1-4000
|
KW1-5000
|
|
Rated current ln (A)
|
|
630
|
800
|
1000
|
1250
|
1600
|
2000
|
2000
|
2500
|
2900
|
3200
|
3600
|
4000
|
4000
|
5000
|
|
Rated operational voltage Ue (V)
|
AC400, 690 50Hz
|
|
Rated insulation voltage Ui (V)
|
AC800 50Hz
|
|
Rated Impulse withstand voltage Uimp (V)
|
8000
|
|
Number of pole
|
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
3, 4
|
|
N pole rated current IN (A)
|
|
50% ln, 100% ln
|
|
Utimate breaking capacity
|
AC400V
|
80
|
80
|
80
|
80
|
80
|
80
|
100
|
100
|
100
|
100
|
100
|
100
|
120
|
120
|
|
Icu (kA)
|
|
AC690V
|
50
|
50
|
50
|
50
|
50
|
50
|
65
|
65
|
65
|
65
|
65
|
65
|
85
|
85
|
|
Rated service breaking
|
AC400V
|
50
|
50
|
50
|
50
|
50
|
50
|
65
|
65
|
65
|
65
|
80
|
80
|
100
|
100
|
|
capacity Ics (kA)
|
AC690V
|
40
|
40
|
40
|
40
|
40
|
40
|
50
|
50
|
|
|
|